Part 8 replaces the prescriptive requirements of Sections 3.2. to 7.2. or the trade-offs of Sections 3.3. and 4.3., Article 8.1.1.1. Note A-1.1.2.1. describes the proof as two energy analyses: one of the building as if it met the prescriptive requirements, which sets the target, and one of the actual design.
When Part 8 can be used
Article 8.1.1.2. applies Part 8 only where the occupancy is known and enough is known about the components. Where information is missing, the prescriptive requirements apply. A design altered during construction must be reassessed, and the method covers one building at a time, though a structure divided by firewalls may be treated as one.
The compliance test (Article 8.4.1.2.)
- The annual energy consumption of the proposed building shall not exceed the building energy target of the reference building.
- Unmet heating hours in each thermal block shall not exceed 100 in the simulated year, for both buildings.
- Unmet cooling hours in the proposed building shall be within ±10% of the reference building's.
The reference building (Subsection 8.4.4.)
Under Article 8.4.4.1., the reference building's components and systems meet the prescriptive requirements of Sections 3.2. to 7.2. Its floor area, use of spaces, thermal blocks, shape, exterior dimensions and orientation are identical to the proposed building's, and it uses the same climatic data. Sentence 8.4.4.3.(3) is the envelope rule examiners like: if the proposed FDWR differs from the maximum in Article 3.2.1.4., the reference FDWR is adjusted proportionally on each orientation until it complies. Sentence 8.4.4.3.(4) leaves permanent shading devices out of the reference building, while Sentence 8.4.3.1.(8) puts them in the proposed model, which is how fins and overhangs earn credit.
The energy model (Subsection 8.4.2.)
Article 8.4.2.2. requires the model to cover heating, cooling, fans, lighting, service water heating, pumps, auxiliary HVAC equipment, receptacle loads, appliances, and elevators and escalators, over 8 760 hours at intervals of one hour or less. Software must conform to ANSI/ASHRAE 140 or an equivalent test method.
What the performance path does not switch off
Each Part's x.4. Section points to Part 8 and lists limits that survive it. Article 3.4.1.2. keeps Article 3.2.1.1. and Subsection 3.2.4., protection of insulation and air leakage, in force. Articles 5.4.1.2. and 6.4.1.2. still require HVAC and service water heating equipment to meet the applicable energy efficiency act or standard. For objective 5.5.2, Article 2.2.2.8. of Division C requires a building performance compliance calculation report with envelope, lighting and HVAC data for both the proposed and reference buildings.