How it lines up with the NBC 2020 and NECB 2020 tiers
The 2020 national codes now use the same pattern as the Step Code: a baseline, then more demanding tiers proved by modelling. That is why the BC guides are useful well outside BC.
NBC 2020 Section 9.36 (Part 9 buildings)
Sentence 9.36.1.3.(1) of Division B lists five ways to comply: prescriptive or trade-off (9.36.2. to 9.36.4.), performance (9.36.5.), tiered performance (9.36.7.), tiered prescriptive (9.36.8.), or the NECB. Sentence 9.36.1.3.(3) limits 9.36.5. and 9.36.7. to houses and to buildings with only dwelling units and common spaces.
- Subsection 9.36.7., tiered performance. Table 9.36.7.2. sets five tiers. For a house over 300 m³ of conditioned space, the percent improvement over the reference house runs from at least 0% at Tier 1 to at least 70% at Tier 5, with a minimum heat loss reduction from Tier 2 up. Sentence 9.36.7.3.(2) caps the peak cooling load at the reference house's: the overheating concern again.
- Subsection 9.36.8., tiered prescriptive. The design earns energy conservation points instead of being modelled. Table 9.36.8.2. requires 10 points for Tier 2 and marks Tiers 3 to 5 "Reserved".
- Subsection 9.36.6., airtightness. It defines ACH50, the same Part 9 metric the Step Code uses, tested under CAN/CGSB-149.10.
NECB 2020 Part 10 (all buildings it covers)
Article 1.1.2.1. of Division B gives three routes: the prescriptive or trade-off requirements of Parts 3 to 7, the performance path of Part 8, or the tiered path of Part 10. Table 10.1.2.1. sets four tiers. Tier 1 is at most 100% of the building energy target, Tier 2 is 75%, Tier 3 is 50% and Tier 4 is 40%, which is a 0%, 25%, 50% or 60% improvement. Sentence 10.1.2.1.(2) says compliance is found by modelling the proposed and reference buildings under Part 8.
A worked example in the style of Note A-10.1.2.1.(2): the reference target is 400 GJ and the proposed design models at 280 GJ. 280 ÷ 400 = 70% of the target, a 30% improvement. That meets Tier 2 (75% or less) but not Tier 3, so the design is Tier 2.
| Feature | BC Energy Step Code | NBC 2020, 9.36.7. and 9.36.8. | NECB 2020, Part 10 |
| Levels | Steps 1 to 5 (Part 9), 1 to 4 (Part 3) | Tiers 1 to 5 | Tiers 1 to 4 |
| Measured against | Absolute targets (TEDI, TEUI or MEUI, ACH50) | Percent of a reference house | Percent of a reference building |
| Proof | Energy model plus airtightness test at every step | Model (9.36.7.) or points (9.36.8.) | Model under Part 8 |
| On the exam | Section 3, objective 13 | Section 2, NBC objectives | Section 2, objective 5.5 |
The main difference: the Step Code sets fixed targets per square metre, while the national tiers are percentages of a reference design. Section 2 tier questions are open book, so tab them; our NBC 2020 tabbing guide and the NECB 2020 study notes cover where they sit.