Thermal bridging: why effective R is lower than nominal R
A thermal bridge is a path where heat bypasses the insulation, through a conductive element or a gap between insulation planes. The BETB Guide v1.6 (p.1) says details that are usually ignored can lead to underestimating 20% to 70% of the total heat flow through walls.
Nominal versus effective
Nominal R is the rating of the insulation product. Effective R is the whole assembly, framing included. Note A-9.36.2.4.(1) of the NBC works an example: a 38 × 140 mm stud wall at 400 mm on centre with RSI 3.34 batts. Framing is 23% of the area, so the stud-and-cavity layer comes out at RSI 2.36, and the whole wall, with sheathing, gypsum and air films added back, reaches RSI 2.78. Note A-9.36.1.2.(3) gives the conversion: 1 (m²·K)/W equals about 5.678 imperial R.
Clear field, linear and point transmittances
| Type | Symbol and unit | What it captures | Examples from the Guide |
| Clear field | Uo, W/(m²·K) | Heat flow per area of a wall, roof or floor, including evenly distributed bridges | Studs, brick ties, girts supporting cladding |
| Linear | ψ (psi), W/(m·K) | Extra heat flow per metre of a linear detail | Slab edges, shelf angles, balconies, parapets, corners, window interfaces |
| Point | χ (chi), W/K | Extra heat flow at one countable spot | A beam through the insulation, intersections of linear details |
Section 3.4 of the Guide adds them up: UT = (Σψ·L + Σχ) / Atotal + Uo. An illustrative wall, with numbers we picked: 100 m² of clear field at Uo = 0.30 W/(m²·K), plus 20 m of uninsulated balcony slab at ψ = 0.50 W/(m·K). The slab adds 10 W/K to the 30 W/K through the clear field, so UT = 0.40 W/(m²·K) and effective RSI falls from about 3.3 to 2.5. Measure the slab where it meets the wall (the plane of heat transfer), not around the balcony's edge.
What the codes say
NECB Article 3.1.1.7.(1) requires thermal bridging to be considered for repetitive framing, major structural penetrations, junctions such as parapets, corners and glazing, and secondary structural members. Note A-3.1.1.5.(5)(a) names the BETB Guide as an acceptable source. Part 9 is lighter: Article 9.36.2.4. counts studs, lintels, sills and plates, lets shelf angles, ties and minor penetrations go, and excuses balcony slabs and beams that stay within 2% of the gross wall area when insulation fits tight around them.
The Guide's performance categories (section 4.2.1) rank uninsulated balconies and shelf angles fixed straight to the slab edge as poor, stand-off shelf angles and thermal breaks better, and continuous exterior insulation best. NBC Sentence 5.3.1.3.(1) adds the condensation angle: where a high-conductance component penetrates the insulation and condensation is likely, enough thermal resistance must be provided there.